Skip to main content
search
NON-CLASSIFIED AREAS GAS DETECTOR

AGS Controls SMART3R Gas Detector

The SMART3R detects toxic, flammable and refrigerant gases in non-classified areas such as machinery rooms, plant rooms and laboratories. You can order it with one of three sensor types: infrared, catalytic or electrochemical. All three versions share the same enclosure, outputs and wiring, so you can mix sensor types on one site and install them the same way.

Features on every version

  • Power: 12-24 Vdc as standard, with an optional AC version
  • Outputs: 3 relays (1.0 A at 30 Vdc), RS485 serial communication and 4-20 mA analogue (4-20 mA on the DC version only)
  • 4 LED status indicators around a transparent ring, plus an internal 63 dB buzzer for alarm and fault conditions
  • Polycarbonate enclosure: 130 x 130 x 74 mm, 1 lb
  • Cable entries: 2 x M20 cable glands, with pre-formed guides for up to 6 additional M16 glands
  • Optional remote sensor head, connected by RJ12 6P6C cable
  • Compliance: EN 378-3, EN 14624, EN 50676, IEC 60335-2-40 Annex LL, ISO 5149-3 and the F-Gas Regulation

Choose your sensor

Infrared (IR)

Use the infrared version for refrigerant gases, CO2 and flammable hydrocarbons. It covers more than 20 refrigerants, including R32, R134a, R410A, R454B, R1234yf and R1234ze, with ranges of 0-2000 ppm, 0-5000 ppm or 0-100% LFL. The sensor has a predicted life of 5 years and responds in under 60 seconds (t90).

Catalytic

Use the catalytic version for combustible gases: methane, LPG, propane, butane and petrol vapours, all with a range of 0-100% LEL. The sensor has a predicted life of 7-10 years.

Electrochemical (EC)

Use the electrochemical version for toxic gases and oxygen: O2, CO, NH3, Cl2, H2S, SO2 and NO2. The sensor has a predicted life of 2-3 years.

Sensor comparison

Infrared Catalytic Electrochemical
Gases Refrigerants, CO2, methane, propane, butane Methane, LPG, propane, butane, petrol vapours O2, CO, NH3, Cl2, H2S, SO2, NO2
Predicted sensor life 5 years 7-10 years 2-3 years
Operating temperature -40 to +140°F, -4 to +122°F or 14 to +122°F, depending on model -22 to +122°F -22 to +122°F
Operating humidity 0-95% RH non-condensing 15-90% RH non-condensing 15-90% RH non-condensing
Current draw 110 mA at 24 Vdc 60 mA at 24 Vdc 60 mA at 24 Vdc
IP rating IP54 IP42 IP42

Product Literature

Part codes: infrared

Flammable gases and refrigerants (0-100% LFL)

Code
Description
S4591ME
Methane gas detector (0 - 100% LFL), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc
S4592PR
Propane gas detector (0 - 100% LFL), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc
S4592BU
Butane gas detector (0 - 100% LFL), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc
S4592DE
R152 gas detector (0 - 100% LFL), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc
S4629R454B
R454B gas detector (0 - 100% LFL), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc
S4626R32
R32 gas detector (0 - 100% LFL), IREF infrared sensor, -40 / +140°F, 12-24 Vdc
S4627R1234YF
R1234YF gas detector (0 - 100% LFL), IREF infrared sensor, 14 / +122°F, 12-24 Vdc
S4628R1234ZE
R1234ZE gas detector (0 - 100% LFL), IREF infrared sensor, 14 / +122°F, 12-24 Vdc

Refrigerants (0-5000 ppm)

Code
Description
S4638R32
R32 gas detector (0 - 5000 ppm), IREF infrared sensor, 14 / +122°F, 12-24 Vdc
S4639R134A
R134a gas detector (0 - 5000 ppm), IREF infrared sensor, 14 / +122°F, 12-24 Vdc
S4640R404A
R404A gas detector (0 - 5000 ppm), IREF infrared sensor, 14 / +122°F, 12-24 Vdc
S4641R407C
R407C gas detector (0 - 5000 ppm), IREF infrared sensor, 14 / +122°F, 12-24 Vdc
S4642R410A
R410A gas detector (0 - 5000 ppm), IREF infrared sensor, 14 / +122°F, 12-24 Vdc
S4643R1234YF
R1234YF gas detector (0 - 5000 ppm), IREF infrared sensor, 14 / +122°F, 12-24 Vdc
S4644R1234ZE
R1234ZE gas detector (0 - 5000 ppm), IREF infrared sensor, 14 / +122°F, 12-24 Vdc
S4857R1233ZD
R1233ZD gas detector (0 - 5000 ppm), IREF infrared sensor, 14 / +122°F, 12-24 Vdc

Refrigerants and SF6 (0-2000 ppm)

Code
Description
S4611R32
R32 gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4612R134A
R134a gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4613SF6
SF6 gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4614R125
R125 gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4615R1234YF
R1234YF gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4616R1234ZE
R1234ZE gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4617R404A
R404A gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4618R407A
R407A gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4619R407F
R407F gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4620R449A
R449A gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4621R507A
R507A gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4622R410A
R410A gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4623R417A
R417A gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc
S4624R448
R448 gas detector (0 - 2000 ppm), IREF infrared sensor, -4 / +122°F, 12-24 Vdc

Carbon dioxide

Code
Description
S4610CO2
CO2 gas detector (0 - 5000 ppm), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc
S4606CO2
CO2 gas detector (0 - 2% Vol), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc
S4607CO2
CO2 gas detector (0 - 5% Vol), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc
S4608CO2
CO2 gas detector (0 - 30% Vol), IRNET infrared sensor, -40 / +140°F, 12-24 Vdc

Add “-220” to get the 220 Vac version
Add “-RH” to get the version with remote head
Add “-220-RH” to get the 220 Vac version with remote head

Part codes: catalytic

Code
Description
S4590ME
Methane gas detector (0 - 100% LEL), 4-20 mA, 12-24 Vdc
S4590GP
LPG gas detector (0 - 100% LEL), 4-20 mA, 12-24 Vdc
S4590PR
Propane gas detector (0 - 100% LEL), 4-20 mA, 12-24 Vdc
S4590BU
Butane gas detector (0 - 100% LEL), 4-20 mA, 12-24 Vdc
S4590VB
Petrol vapours gas detector (0 - 100% LEL), 4-20 mA, 12-24 Vdc

Add “-220” to get the 120 Vac version
Add “-RH” to get the version with remote head
Add “-220-RH” to get the 120 Vac version with remote head

Part codes: electrochemical

Code
Description
S4593O2
Oxygen gas detector (0 - 25% Vol), 12-24 Vdc
S4595CO
Carbon monoxide gas detector (0 - 500 ppm), 12-24 Vdc
S4597AM
Ammonia gas detector (0 - 100 ppm), 12-24 Vdc
S4598AM
Ammonia gas detector (0 - 200 ppm), 12-24 Vdc
S4599AM
Ammonia gas detector (0 - 1000 ppm), 12-24 Vdc
S4634CL
Chlorine gas detector (0 - 20 ppm), 12-24 Vdc
S4601HS
Hydrogen sulphide gas detector (0 - 50 ppm), 12-24 Vdc
S4630SD
Sulphur dioxide gas detector (0 - 20 ppm), 12-24 Vdc
S4632ND
Nitrogen dioxide gas detector (0 - 20 ppm), 12-24 Vdc

Add “-220” to get the 120 Vac version
Add “-RH” to get the version with remote head
Add “-220-RH” to get the 120 Vac version with remote head