Skip to main content

Carbon Monoxide Boiler Interlock

Code Required in Florida, Georgia, New York & Texas

AGS Mini Merlin

If there is a dangerous build-up of gas or unsafe levels of carbon monoxide at the sensor, this device can shut off the gas supply via a gas safety valve and/or a gas fire appliance. A code requirement in Florida, Georgia & Texas.

This device has additional features for resetting systems, as well as audible and visual alarms – it can also be integrated with a Building Management System (BMS). For further information on our Mini Merlin refer to our datasheets or alternatively contact our offices today.

Plug & Play Installation – Pre-Programmed Inputs & Outputs

POWER/LINE IN Mains Input: 100-120V ~ 50/60Hz
VALVE OUT Gas Valve Power Output: 100-120V ~ 50/60Hz
Auto Reset & Buzzer Switches
BMS CO 0.5A SWITCHING CURRENT (RESISTIVE LOAD) Switches when CO gas reaches alarm level or if detector encounters a power failure.
REMOTE SHUT OFF Open / Close Circuit Connector Shuts off gas valve if external devices are activated i.e. fire alarm etc
BMS NG/LPG 0.5A SWITCHING CURRENT (RESISTIVE LOAD) Switches when Methane/LPG gas reaches alarm level or if detector encounters a power failure.
Anti-Surge 3.15A 250Vac Fuse, Wire Rating Min. 18AWG, Tinned Copper @ 167°F
Gas Level & TFT Status Display
ULC Listed 61010
Manual Reset After Alarm Condition
Audible & Visual Alarm

Carbon Monoxide Interlock Code Requirements

In Texas, Florida & Georgia, a carbon monoxide detector is required with all new & refurbished boiler(s) installations to automatically shutdown the boiler(s) in the event of high CO levels. See below a summary of the existing codes.

Florida

Florida Compliant - Rule Chapter: 69A-70

509.211 Safety regulations

(4) Requires that every enclosed space or room that contains a boiler regulated under chapter 554 which is fired by the direct application of energy from the combustion of fuels and that is located in any portion of a public lodging establishment that also contains sleeping rooms shall be equipped with one or more carbon monoxide sensor devices that bear the label of a nationally recognized testing laboratory and have been tested and listed as complying with the most recent Underwriters Laboratories, Inc., Standard 2034, or its equivalent, unless it is determined that carbon monoxide hazards have otherwise been adequately mitigated as determined by the division. Such devices shall be integrated with the public lodging establishment’s fire detection system. CO METERS by set to shut boiler off and 35ppm and Must have a Manual Reset.

Georgia

2022 Rules & Regulations of the State of Georgia - Rule 120-3-26-.07

120-3-26-.07 (10) – State Inspection Fees New Installation of Boilers and Installation of Secondhand Boilers or Pressure Vessels

(a) Each boiler room containing one or more boilers or hot water heaters or pressure vessels from which carbon monoxide can be produced shall be equipped with a carbon monoxide detector with a manual reset. The requirements of this subsection apply to boiler rooms in which new installations or re installations of one or more boilers are completed.
(1) The carbon monoxide detector will alarm at 50 ppm and boiler(s) shall be interlocked to disable the burners when the measured level of carbon monoxide rises above 200 ppm.
(2) The carbon monoxide detector shall disable the burners upon loss of power to the detector.
(3) When the carbon monoxide detector trips in the boiler room, the detector should be interlocked with all boilers or hot water heaters or pressure vessels installed in the space to secure the fuel burning equipment thus stopping the production of carbon monoxide.
(4) The carbon monoxide detector shall be calibrated every eighteen months after installation or in accordance with the manufacturer’s recommendations, whichever is more frequent. A record of calibration shall be posted at or near the boiler or be readily accessible to an inspector.
(5) The carbon monoxide detector shall be installed and function in accordance with all other regulations and standards adopted by the Commissioner.
(6) Any boiler room that is monitored by a full-time boiler operator is exempt from the safety shutdown, as defined in ASME CSD-1. The presence of a full-time boiler operated does not exempt such boilers from the alarm requirement.

New York

Chapter 908-01 - Carbon Monoxide Detectors

§908-01 Carbon Monoxide Detectors.
(a) Scope. Pursuant to sections 908.7.2 and 908.7.3 of the Building Code (BC), listed carbon monoxide (CO) detectors required to be installed in E, I-2 and I-4 occupancies and in buildings equipped with a fire alarm system that contain Group A-1, A-2, A-3, B or M occupancies, as defined in BC Chapter
3, must be installed in accordance with the requirements of this section.
(1) These requirements do not apply to those R-2 occupancies that are adjacent to or above those occupancies classified in this section.
(2) Pursuant to BC section 908.7.3.1, existing buildings must comply with the requirements of this subdivision by July 1, 2021.

(b) Reference. See section 28-315.11 of the New York City Administrative Code (AC), and BC sections 908.7.2, 908.7.3, 908.7.3.1 and 908.7.4. (c) Group E, I-2 and I-4 occupancies. CO detectors with built-in sounder bases installed in E, I-2 and I-4 occupancies in accordance with BC 908.7.2 must be installed in the following locations:
(1) Any room containing carbon monoxide-producing equipment, except kitchens and laboratories.
(2) Any corridor on the story where carbon monoxide-producing equipment unit is located, as well as one story above and one story below.

(d) Group A-1, A-2 and A-3 occupancies. CO detectors with built-in sounder bases installed in buildings that are equipped with a fire alarm system and that contain A-1, A-2 or A-3 occupancies must be installed in the following locations:
(1) Any room containing CO-producing equipment, except kitchens.
(2) Any occupiable room or space on the same floor as, one story above, or one story below the CO-producing equipment that is at least 75 square feet and is not provided with mechanical ventilation.

(e) Group B and M occupancies. CO detectors with built-in sounder bases installed in buildings that are equipped with a fire alarm system and that contain Group B or M occupancies must be installed in the following locations:
(1) Any room containing CO-producing equipment, except kitchens.
(2) Any corridor on the story where carbon monoxide-producing equipment unit is located, as well as one story above and one story below.

(6) Detection zones:
(i) Detection zones less than 10,000 square feet. Where carbon monoxide detection is required to be provided in a detection zone having an area less than 10,000 square feet, the carbon monoxide detection shall be placed in a central location within such detection zone.
(ii) Detection zones 10,000 square feet or greater. Where carbon monoxide detection is required to be provided in a detection zone having an area 10,000 square feet or greater, carbon monoxide detection shall be placed in a central location within such detection zone and at such additional locations with such detection zone as may be necessary to assure that no point in the detection zone is more than 100 feet from carbon monoxide detection.

(f) Equipment shutdown. Activation of a CO detector located at the source of CO-producing equipment must shut down that source. This provision does not apply where the source is a generator.

(g) Installation requirements. CO detectors must be installed in accordance with NFPA 720 – 2015 edition, as modified for New York City by this section.

(h) Fire alarm control units. The provisions of section 23.8.2.2 of NFPA 72 – 2010 regarding having a separate panel apply to CO detectors.

Texas

16 Texas Administrative Code (TAC) Chapter 65

Each boiler room containing one or more boilers from which carbon monoxide can be produced shall be equipped with a carbon monoxide detector with a manual reset.

(1) The carbon monoxide detector and boiler(s) shall be interlocked to disable the burners when the measured level of CO rises above 50ppm.

(2) The carbon monoxide detector shall disable the burners upon loss of power to the detector.

(3) The carbon monoxide detector shall be calibrated in accordance with the manufacturer’s  recommendations or every eighteen months after installation of the detector. A record of calibration shall be posted at or near the boiler, or be readily accessible to an inspector.

(4) The requirements in this subsection apply to boiler rooms in which need installations or re-installations of one or more boilers are completed on or after September 1, 2020.’

ASME CSD-1 Code Requirement

‘(b) A manually operated remote shutdown switch or circuit breaker shall be located just outside the boiler room door and marked for easy identification.

(1) Consideration should be given to the type and locations of remote shutdown switch to safeguard against tampering. If the boiler room door is on the building exterior, the switch should be located just inside the door. If there is more than one door to the boiler room, there should be a remote shutdown switch located at each door.
(2) Activation of the remote switch or circuit breaker shall immediately shut off the fuel or energy supply.’