Cannabis Cultivation CO2 Monitoring

Advanced Indoor Air Quality Sensing Technology

38.5.3.2.1 The system shall be designed as follows:
(1) Activates a low-level alarm upon detection of a carbon dioxide concentration of 5000ppm.
(2) Activates a high-level alarm upon detection of a carbon dioxide concentration of 30,000ppm.

38.5.3.2.2 System Activation
38.5.3.2.2.1
Activation of the low-level gas detection system shall automatically initiate the following:
(1) Stop the flow of carbon dioxide to the piping system.
(2) Activate the mechanical exhaust ventilation system.
(3) Activate an audible and visible supervisory alarm signal at an approved location within the building.


38.5.3.2.2.2 
Activation of the high-level gas detection system alarm shall automatically initiate the following:
(1) Stop the flow of carbon dioxide to the piping system.
(2) Activate the mechanical exhaust ventilation system.
(3) Activate an audible and visible evacuation alarm both inside and outside of the carbon dioxide encirclement area and the area in which the carbon dioxide containers are located.

38.5.3.3 Pressurization and Ventilation.
(2) When activated by the gas detection system, the mechanical ventilation system shall remain on until manually reset.’

The Merlin CO2 X comes with this functionality & more. 

Cannabis Cultivation Carbon Dioxide Monitoring Solution

AGS CO2 X Spec Sheet
AGS CO2 X User Manual

The AGS CO2 X is designed to monitor carbon dioxide (CO2) in the air, local temperature in cannabis cultivation factories. This monitor can be used as a standalone unit to automatically drive exhaust fans to reduce CO2 and temperature as well  shutting off CO2 gas supplies in high level alarm.

Using relays and 0-10vdc outputs the unit can interface with all modern BAS systems & fire panels. The continuous CO² self-recalibration feature eliminates the need for routine maintenance.

For further information check out our download section or alternatively contact your local representative – Click Here

• CO2 measured and displayed in parts per million (ppm).
• Automatically ramp exhaust fans dependant on CO2 levels via a 0-10V DC output
• Shutdown CO2 Gas Lines if High Levels of CO2 is detected
• Dual power 110V AC or 24V AC.
• Temperature can be displayed in degrees Celsius (°C) or Fahrenheit (°F).
• 0-10V Signal Output progress bar display.
• Monitor, record and display average CO2 concentration over 8 hour periods.
• User friendly settings menu.
• Pre-alarm and alarm relay output.
• Fan controller enabled relay output.
• End of Life and Fault notifications for CO2 sensing element.
• Ventilation Boost, Mute and Screen Wake Up button.